Products
For applications with large power requirements such as large residential, commercial or village power systems. The FLEXware 1000 system architecture is capable of supporting up to four OutBack FX Series Inverter/Chargers, four OutBack charge controllers, and all the required AC and DC components and wiring. Utilizing a compact design, FLEXware 1000 AC and DC enclosures accommodate all of the essential protective devices with lots of room for additional breakers and large cable connections and can be mounted either vertically or horizontially.
FLEXware 1000 Specifications
Model: FW1000-DC
DC enclosure which mounts at the
DC side of three or four FX Series Inverter/Chargers. Supports
up to eight terminal bus bars (not including GBB) and up to three
shunt assemblies depending on configuration
Includes: Ground bus bar, 1000 Amp DC shunt assembly, positive bus, breaker mounting hardware, enclosure mounting hardware, two FW-SBUSs and one FLEXware 1000 breaker bus
| Unit Dimensions (H x W x D) | Shipping Dimensions (H x W x L) | Shipping Weight | Enclosure Type |
|---|---|---|---|
| 38.5 x 11.4 x 12.1" (97.8 x 29.0 x 30.7 cm) | 14.5 x 13.6 x 40.6" (36.8 x 34.5 x 103.1 cm) | 21 lbs. (9.5 kg) | Type-1 indoor (IP30) |
Model: FW1000-AC
AC enclosure which mounts at the
AC side of three or four FX Series Inverter/Chargers. Supports
eight terminal bus bars and one FW-X240. The FW1000 system
utilizes two FW-MPs (mounting plates) and a set of the DCA
and ACA conduit adapters for each inverter/charger. DC and AC
breakers, Input-Output-Bypass Assemblies and all other
additional components sold separately.
Includes: Ground bus bar, two DIN mounting brackets and FLEXware 1000 wiring raceway
| Unit Dimensions (H x W x D) | Shipping Dimensions (H x W x L) | Shipping Weight | Enclosure Type |
|---|---|---|---|
| 38.5 x 11.4 x 12.1" (97.8 x 29.0 x 30.7 cm) | 14.5 x 13.6 x 40.6" (36.8 x 34.5 x 103.1 cm) | 21 lbs. (9.5 kg) | Type-1 indoor (IP30) |
FLEXware 1000 AC Input-Output-Bypass Assemblies
Model: FW-IOB-T-120/208VAC
Field installable kit for bypassing the AC input to the AC output
for inverter maintainence or installation. Also provides
over-current protection.
Includes: Nine 60A 120VAC single pole DIN mount breakers, sliding bypass interlock plate, wire and hardware kit
| System Rating | Bypass Breaker | Input Breaker | Output Breaker |
|---|---|---|---|
| Three-Phase 120/208 VAC 60 Amps 21.6 kW |
Three Poles @ 60 Amps 21.6 kW |
Three Poles @ 60 Amps 21.6 kW |
Three Poles @ 60 Amps 21.6 kW |
Model: FW-IOB-T-230/400VAC
Includes: Nine 30A 230VAC single pole DIN
mount breakers, sliding bypass interlock plate, wire and hardware kit
| System Rating | Bypass Breaker | Input Breaker | Output Breaker |
|---|---|---|---|
| Three-Phase 230/400 VAC 30 Amps 20.7 kW |
Three Poles @ 30 Amps 20.7 kW |
Three Poles @ 30 Amps 20.7 kW |
Three Poles @ 30 Amps 20.7 kW |
Model: FW-IOB-Q-120/240VAC
Includes: Eight 60A 120VAC single pole DIN
mount breakers, two 60A 120VAC dual pole DIN mount breakers,
sliding bypass interlock plate, wire and hardware kit
| System Rating | Bypass Breaker | Input Breaker | Output Breaker |
|---|---|---|---|
| Split Phase 120/240 VAC 120 Amps 28.8 kW |
Four Poles @ 60 Amps 28.8 kW |
Four Poles @ 60 Amps 28.8 kW |
Four Poles @ 60 Amps 28.8 kW |
Model: FW-IOB-Q-230VAC
Includes: Twelve 30A 230VAC single pole DIN
mount breakers, sliding bypass interlock plate, wire and hardware kit
| System Rating | Bypass Breaker | Input Breaker | Output Breaker |
|---|---|---|---|
| Single-Phase 230 VAC 120 Amps 27.6 kW |
Four Poles @ 30 Amps 27.6 kW |
Four Poles @ 30 Amps 27.6 kW |
Four Poles @ 30 Amps 27.6 kW |
- FLEXware ACA AC Conduit Adapter User's Guide - Includes Mounting and Installation (308KB PDF)
- FLEXware Mounting Plate User's Guide - Includes Mounting, Installation, and Product Registration (1.3MB PDF)
- FW-1000 Includes Mounting, Installation, and Product Registration (9MB PDF)
- FW-IOB-Q-120VAC Input/Output/Bypass Assembly Installation Instructions (1.4MB PDF)
- FW-IOB-Q-230VAC Input/Output/Bypass Assembly Installation Instructions (1MB PDF)
- FW-IOB-Q-240VAC Input/Output/Bypass Assembly Installation Instructions (960KB PDF)
- FW-IOB-T-120/208VAC Input/Output/Bypass Assembly Installation Instructions (1.2MB PDF)
- FW-IOB-T-230/400VAC Input/Output/Bypass Assembly Installation Instructions (1.2MB PDF)
Spotlight
Expanded Technical Support Hours
6am to 5pm PST
360.618.4363